Electric Co., Ltd. Yueqing Dengrui factory direct【LXQ3 voltage transformer neutral point with resonance eliminator】,And provide a variety of【LXQ3 voltage transformer neutral point with resonance eliminator】Images, parameters, description and other detailed product information,Dengrui【LXQ3 voltage transformer neutral point with resonance eliminator】High quality, excellent price, special requirements can be customized consultation.
LXQ (3) type 6 ~ 35KV voltage transformer neutral point of the
nonlinear harmonic elimination damper resistance (referred to as
resonance eliminator), is installed in the 6 ~ 35KV voltage transformer (hereinafter
referred to as the pressure change or PT) time winding Y . Tie line
between neutral and earth resistance of a non-linear harmonic
elimination damping devices. Resonance eliminator of the product
model - LXQ that the design of the traditional rectangular shape of
resonance eliminator; LXQ3 said third modification design, the
resistor looks naked without the protection insulated jacket,
cylindrical shape of the resonance eliminator. Only two different
shape, the same electrical performance.
LXQ (3) type 6 ~ 35KV resonance eliminator DC electrical characteristics with the traditional RXQ and LXQ
type resonance eliminator similar, but improved harmonic
elimination from the structural design of the heat capacity, to
conduct a greater improvement. Harmonic elimination uses electrical
performance, ultra-fine particles of SiC as a substrate; by large
tonnage presses pressed into high-density, round pie of the green
body; in reducing atmosphere; by thousands of degrees of
high-temperature sintering . Bare resistor surface structure
specially treated to withstand sun and rain, can be directly used
for indoor and outdoor. Dengrui electrical resonance eliminator of
small size, light weight, fast heat, high strength, easy to
install, very popular with users.
Features
* Eliminate or damping caused by the voltage transformer
ferroresonance, voltage transformer to avoid internal and external
insulation breakdown, discharge;
* Limit the system or in single-phase flow through the arc to
ground through transformer winding current and voltage transformers
to avoid burning;
* Small size, light weight, convenient and flexible, easy to
install.
Voltage transformer with a neutral point of the electrical parameters of Table resonance eliminator
Voltage | DC Characteristics | nonlinear coefficient | AC 0.3mA (V Peak/√2) | AC 3mA (V Peak/√2) | Heat capacity |
6kV、10kV | 1.45~1.65/15 | 0.40~0.45 | 130±50 | 500 |